Signal and supply return may share a conductor when the sensor and receiving input are designed for that topology. The cable alone cannot decide this. Confirm the sensor's output circuit, the input's reference arrangement and their permitted operating conditions. A shared conductor can carry supply current and also set a signal reference, so impedance in that path can influence the measured result. Adding a separate return without checking the equipment can create a different, equally unsuitable circuit.
“Zero volts” needs a circuit definition
A wiring sketch marked “0 V” can hide several roles: a power return, an analog reference, a digital input common, a cable screen or a protective connection. Those labels do not make the conductors interchangeable. Obtain the sensor and input-module connection diagrams before deciding how many cores the assembly needs.
A two-wire device, a three-wire sensor with a common return and an output requiring separate signal connections are different circuit arrangements. A differential input is also not automatically isolated, and its common-mode range still matters. Record the actual equipment arrangement instead of creating a preferred grounding scheme from the number of connector contacts available.
Analog Devices describes single-ended, pseudo-differential and fully differential converter inputs as distinct interfaces with different requirements. The useful lesson for an assembly specification is to preserve the interface defined by the equipment designer. A cable supplier should not have to infer it from “sensor cable” or from a connector photograph.

The shared section is where the question becomes useful
Consider a hypothetical analog sensor whose supply current and output reference use a common return path. If another load's current also flows through part of that path, the reference seen by the receiver may change. The effect depends on the circuit, the impedance involved and how the input measures the signal. This is a common-impedance question, not proof that every shared-return sensor connection is faulty.
Draw the return paths through the sensor, cable, terminal connections and input module. Mark where current paths join and where the signal is referenced. A star drawn on a schematic is insufficient if the physical installation adds a shared terminal bridge or conductor elsewhere. Equally, do not remove an equipment-required connection simply because the drawing contains more than one return path.
Analog Devices' grounding guidance explains how currents sharing an impedance can couple into another circuit. It provides a mechanism to investigate, not a numerical error prediction for an unidentified KMYD assembly. The equipment designer needs the actual topology and operating conditions to judge whether the resulting reference variation is acceptable.
Collect the interface evidence before changing cores
- Sensor output: record the output type, its connection diagram and the manufacturer's specified relationship between supply return and signal reference.
- Receiving input: identify its terminal arrangement, reference, isolation status where specified and applicable input or common-mode limits.
- Shared loads: identify other currents using the same return section, including any equipment-defined operating states that matter.
- Physical path: show the actual junctions and any separately required screen or protective connections.
- Acceptance basis: let the responsible designer select a verification method and criterion appropriate to the measurement or switching function.
These inputs answer a narrower question than a cable current rating or a loaded voltage-drop calculation: what role is each conductor permitted to play in this circuit? Establishing that role comes first. Conductor sizing and other electrical checks remain necessary where relevant, but changing wire size cannot correct an interface that was connected contrary to its manual.
Keep the screen on its own documented path. It is not a spare signal-return conductor. Protective conductors have another purpose again. If an equipment drawing does not make the distinction clear, raise that ambiguity before the cable's connection table is released.

Hand the supplier a circuit decision
If a noise or measurement issue prompts the review, preserve the existing equipment configuration and symptoms for the responsible engineer. Identify which loads were operating and which input was affected. Do not experiment with energized return connections or protective paths to discover a preferred arrangement. A controlled investigation needs the equipment's procedures and appropriate personnel.
KMYD's custom M12 assembly and customized M8 cable offering are routes for specifying the resulting lead. Send the agreed circuit diagram and conductor-role table, naming the sensor and input revisions. Ask the supplier to implement that definition, with any unresolved common-return question returned to the equipment designer rather than settled by a generic connector pinout.